Gates Data Center Cooling Solutions
Gates
Gates' 2025 brochure presents zinc-free peroxide-cured EPDM data centre hoses, UQD/MQD couplings and ThermalCool pumps rated 2.1 kW, 200 L/min at 3 bar in one product overview.
On this page
Overview
The brochure collects Gates' liquid cooling components for managing heat from AI and cloud workloads: hoses, couplings, pumps and power transmission products. The hose family is Data Master, described as OCP-accepted.
Data Master hoses serve server trays and rack manifolds in 7/32, 1/4, 3/8, 1/2, 3/4 and 1 inch ID, and the MegaFlex series serves rack source lines in 1, 1.25, 1.5, 2, 3 and 4 inch ID. The tube is zinc-free peroxide-cured EPDM, with cleanliness, UL94V-0 flame resistance, flexibility and coolant compatibility including PG25 highlighted. Blue (supply) and red (return) colours are available.
The coupling family includes OCP-compliant UQD/B, compact MQD/B (hand-mate or blind-mate), low pressure drop full-flow couplings (300 L/min) and Tri-Clamp couplings. ThermalCool 2100 pumps are 2.1 kW with a three-phase 48 V axial-flux BLDC motor, delivering 200 L/min at 3 bar, in nickel-plated aluminium or stainless steel, manifold or bracket mounted. MegaFlex assemblies are part of the OCP Deschutes CDU specification. The document is a product brochure without detailed engineering data.
Key points
- Data Master hoses come in 7/32 to 1 inch ID; MegaFlex hoses in 1 to 4 inch ID.
- The tube is zinc-free peroxide-cured EPDM, tested to UL94V-0.
- Hoses are compatible with a wide range of coolant mixes including PG25; blue supply and red return colours exist.
- Full-flow couplings are rated 300 L/min with ball-valve control for minimal pressure drop.
- MQD/B couplings have stainless steel construction and EPDM seals, with hand-mate or blind-mate versions.
- ThermalCool 2100 pumps are 2.1 kW, 48 V BLDC, 200 L/min at 3 bar.
- MegaFlex assemblies are part of the OCP Deschutes CDU specification.
- Quad-Power 4 belts claim up to 98% total power efficiency; Poly Chain GT Carbon covers -54 to +85 °C.
Using it in design
- Choose hose ID from Data Master sizes for tray and manifold lines and MegaFlex sizes for rack source lines.
- Separate supply and return lines with colour-coded hose to reduce misconnection risk.
- Specify OCP-compliant UQD/B or MQD/B couplings and verify seal compatibility with the coolant (PG25).
- Use 200 L/min at 3 bar as the reference point for CDU pump selection and compare it with the real circuit curve.
- Write UL94V-0 compliance into the hose specification where flame resistance is required.
Who should read it
Mechanical engineers and procurement teams selecting liquid cooling loop, CDU and manifold components.
Document contents
- The Gates difference
- Data Master cooling hoses
- Data center couplings
- ThermalCool data center pumps
- Gates power transmission products
Publication details
- Authors
- Gates
- Publisher
- Gates
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Gates (2025). Gates Data Center Cooling Solutions. Gates. https://www.gates.com/content/dam/documents-library/brochures/data-center-cooling-solutions-brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.