Gates Data Center Cooling Solutions

Gates

Gates' 2025 brochure presents zinc-free peroxide-cured EPDM data centre hoses, UQD/MQD couplings and ThermalCool pumps rated 2.1 kW, 200 L/min at 3 bar in one product overview.

On this page

Overview

The brochure collects Gates' liquid cooling components for managing heat from AI and cloud workloads: hoses, couplings, pumps and power transmission products. The hose family is Data Master, described as OCP-accepted.

Data Master hoses serve server trays and rack manifolds in 7/32, 1/4, 3/8, 1/2, 3/4 and 1 inch ID, and the MegaFlex series serves rack source lines in 1, 1.25, 1.5, 2, 3 and 4 inch ID. The tube is zinc-free peroxide-cured EPDM, with cleanliness, UL94V-0 flame resistance, flexibility and coolant compatibility including PG25 highlighted. Blue (supply) and red (return) colours are available.

The coupling family includes OCP-compliant UQD/B, compact MQD/B (hand-mate or blind-mate), low pressure drop full-flow couplings (300 L/min) and Tri-Clamp couplings. ThermalCool 2100 pumps are 2.1 kW with a three-phase 48 V axial-flux BLDC motor, delivering 200 L/min at 3 bar, in nickel-plated aluminium or stainless steel, manifold or bracket mounted. MegaFlex assemblies are part of the OCP Deschutes CDU specification. The document is a product brochure without detailed engineering data.

Key points

  1. Data Master hoses come in 7/32 to 1 inch ID; MegaFlex hoses in 1 to 4 inch ID.
  2. The tube is zinc-free peroxide-cured EPDM, tested to UL94V-0.
  3. Hoses are compatible with a wide range of coolant mixes including PG25; blue supply and red return colours exist.
  4. Full-flow couplings are rated 300 L/min with ball-valve control for minimal pressure drop.
  5. MQD/B couplings have stainless steel construction and EPDM seals, with hand-mate or blind-mate versions.
  6. ThermalCool 2100 pumps are 2.1 kW, 48 V BLDC, 200 L/min at 3 bar.
  7. MegaFlex assemblies are part of the OCP Deschutes CDU specification.
  8. Quad-Power 4 belts claim up to 98% total power efficiency; Poly Chain GT Carbon covers -54 to +85 °C.

Using it in design

  • Choose hose ID from Data Master sizes for tray and manifold lines and MegaFlex sizes for rack source lines.
  • Separate supply and return lines with colour-coded hose to reduce misconnection risk.
  • Specify OCP-compliant UQD/B or MQD/B couplings and verify seal compatibility with the coolant (PG25).
  • Use 200 L/min at 3 bar as the reference point for CDU pump selection and compare it with the real circuit curve.
  • Write UL94V-0 compliance into the hose specification where flame resistance is required.

Who should read it

Mechanical engineers and procurement teams selecting liquid cooling loop, CDU and manifold components.

Document contents

  1. The Gates difference
  2. Data Master cooling hoses
  3. Data center couplings
  4. ThermalCool data center pumps
  5. Gates power transmission products

Publication details

Authors
Gates
Publisher
Gates
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Gates (2025). Gates Data Center Cooling Solutions. Gates. https://www.gates.com/content/dam/documents-library/brochures/data-center-cooling-solutions-brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.