Liquid Cooling in Data Centres (IEA 4E EDNA, June 2026)
Original title Liquid Cooling in Data Centres
IEA 4E EDNA · Anson Wu, Jan Viegand
A June 2026 IEA 4E EDNA report finding that liquid cooling cuts IT load by up to 8% inside the server and cooling energy by about 30-40% at facility level, for overall data centre energy savings of 10-21%.
On this page
Overview
The report examines three liquid cooling families, direct-to-chip (DTC), immersion (IC) and rear-door heat exchangers (RDHx), together with energy savings potential, market status and policy implications. Single-phase DTC is the most mature and widely deployed, at about 43% of liquid cooling market revenue; immersion is the fastest-growing segment. The main factor shaping system performance and heat reuse is the heat rejection side: whether CDUs reject heat into the hall via liquid-to-air (LTA) or directly into the facility water system (FWS) via liquid-to-liquid (LTL).
Energy savings come from two sources: reduced or eliminated fan power inside the server cuts IT load by up to 8%, and at facility level, displacing chillers and air handlers cuts cooling energy by about 30-40%. Overall data centre energy savings are on the order of 10-21%. Using the IEA 4E TEM 4.0 model, a realistic hybrid DTC scenario for non-AI data centres could save about 22.6 TWh a year by 2030 (11% of consumption) and an optimised immersion scenario about 70.8 TWh (34%); AI data centres are excluded.
In AI hardware, leading GPU TDPs now exceed 1,000 W per chip and liquid cooling is a prerequisite for high-density AI. Liquid cooling yields higher-grade waste heat of 45-70 °C, but reuse needs LTL-CDUs, off-taker proximity, demand matching, contractual frameworks and supportive policy. About 22% of data centres use some liquid cooling; 48% use it in under 10% of racks and 61% of operators are considering it. Main barriers are lack of standardisation (39%), high initial cost (38%) and long-term reliability concerns (35%).
The policy section says PUE systematically understates liquid cooling gains and proposes, as an interim measure, a standardised PUE adjustment factor by cooling system type, then TUE and an Enhanced Energy Reuse Factor (EERF) reflecting heat grade. PUE targets of 1.2 in China and Singapore are de facto mandates for liquid cooling. In non-AI facilities, liquid cooling is economical above roughly 20 kW per rack at the high internal discount rates operators apply.
Key points
- Three technology families: DTC, immersion and RDHx; single-phase DTC is the most widely deployed at about 43% of revenue.
- In-server saving: reduced fan power cuts IT load by up to 8%.
- Facility cooling energy falls by about 30-40% and overall data centre energy by about 10-21%.
- 2030 model, non-AI: hybrid DTC about 22.6 TWh a year (11%), optimised immersion about 70.8 TWh (34%).
- GPU TDPs exceed 1,000 W per chip; the IEA projects global data centre electricity at about 945 TWh by 2030.
- Liquid cooling gives 45-70 °C waste heat; reuse needs LTL-CDUs, off-taker proximity and contractual frameworks.
- About 22% of data centres use liquid cooling; 48% in under 10% of racks; 61% are considering it.
- Barriers: lack of standardisation 39%, high initial cost 38%, reliability concerns 35%; liquid cooling is economical above about 20 kW per rack.
Using it in design
- Decide the CDU type (LTA or LTL) at the start of design: heat reuse needs LTL-CDUs and an FWS connection.
- Calculate savings separately for in-server fan reduction (up to 8% of IT load) and facility-side cooling (about 30-40%).
- Do not rely on PUE alone for benchmarking: liquid cooling gains look small in PUE, so track IT and cooling energy separately.
- In planning, match 45-70 °C waste heat to a heat off-taker such as district heating.
- Include floor loading limits of existing multi-storey buildings in retrofit feasibility.
- Prioritise the liquid cooling case in halls with rack densities above about 20 kW.
Who should read it
Data centre operators, designers, regulators and energy analysts setting liquid cooling strategy and policy.
Document contents
- Executive summary
- Introduction
- Technology overview
- System-level impact analysis
- Reuse of data centre waste heat
- Implementation scenarios and operational considerations
- Market and business dynamics
- Artificial intelligence and liquid cooling
- Global energy savings potential
- Potential policy implications
- Conclusions
- Appendix: equipment vendors
Publication details
- Authors
- Anson Wu; Jan Viegand
- Publisher
- IEA 4E EDNA
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Anson Wu; Jan Viegand (2026). Liquid Cooling in Data Centres. IEA 4E EDNA. https://www.iea-4e.org/wp-content/uploads/2026/02/EDNA-2026-LIQUID-COOLING-IN-DATA-CENTRES3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.