Material Compatibility Guide: Compuzol Immersion Cooling Fluids

Original title CompuZol Immersion Cooling: Material Compatibility Guide

Lubrizol

Lubrizol's 2023 guide classifies compatibility of common hardware materials with CompuZol dielectric fluids from immersion tests of 3 days at 110 °C, 5 days at 80 °C and 7 days at 70 °C.

On this page

Overview

The guide gives compatibility of common data centre hardware with Lubrizol CompuZol dielectric immersion cooling fluids. Compatibility has three levels: compatible (passed all testing, minor changes acceptable), partially compatible (some change occurred, may be acceptable in specific applications) and not recommended (component ceased to function, lost structural integrity or leached contaminants affecting fluid properties).

There are three test groups. CPU package materials, thermal interface materials and thermal greases were soaked three days at 110 °C; silicone-based grease and pads showed fluid haze, silicone polymer leaching and loss of structural integrity, and hydrocarbon-based thermal pad disintegrated. Server and board components were soaked five days at 80 °C; PVC insulated cables showed plasticiser leaching and rigidity, power supplies showed haze attributed to TIM, and motherboard TIM under the heat spreader degraded, while memory and storage PCBs, metal heatsinks, coin cell batteries and aluminium organic polymer capacitors showed no change.

Elastomers, plastics and seals were soaked seven days at 70 °C. Polypropylene, HDPE, nylon (PA66), polyurethane, PPE, non-plasticised PVC, PEEK, PPS and FKM showed no visible change; PET and braid-reinforced silicone tubing warped and LDPE yellowed. Nitrile (NBR) seals, EPDM and natural rubber (polyisoprene) swelled, with pitting and fluid browning for EPDM and natural rubber; plasticised PVC is not recommended. Advanced analytical and physical property testing was added. The results are laboratory data, and the guide states that products must be thoroughly tested before commercialisation.

Key points

  1. Three compatibility levels: compatible, partially compatible, not recommended.
  2. CPU package, TIM and grease test: 3 days at 110 °C.
  3. Server and board component test: 5 days at 80 °C.
  4. Elastomer, plastic and seal test: 7 days at 70 °C.
  5. Silicone-based grease and pads showed haze, silicone leaching and lost integrity; the hydrocarbon-based pad disintegrated.
  6. PVC insulated cables showed plasticiser leaching and rigidity; plasticised PVC is not recommended.
  7. PP, HDPE, PA66, PU, PPE, non-plasticised PVC, PEEK, PPS and FKM showed no visible change.
  8. NBR, EPDM and natural rubber swelled; EPDM and natural rubber also pitted and browned the fluid.
  9. Memory and storage PCBs, metal heatsinks, coin cell batteries and aluminium organic polymer capacitors showed no change.

Using it in design

  • In the immersion bill of materials, flag silicone-based grease and pads, plasticised PVC cable and NBR, EPDM and natural rubber seals and replace them with alternatives.
  • Consider FKM for seals and PP, HDPE or PA66 for hose and tank parts, since they showed no visible change.
  • In TIM selection, check the effect of PSU and motherboard interface materials on the fluid.
  • Compare the test conditions (70-110 °C, 3-7 days) with your operating temperature and run longer tests if needed.
  • Verify all guide decisions with your own server model before commercialisation.

Who should read it

Engineers designing immersion-ready servers and tanks, and materials and procurement specialists.

Document contents

  1. Overview and compatibility definitions
  2. CPU package materials, thermal interface materials and thermal greases
  3. Server and board components
  4. Elastomers, plastics and seal materials
  5. Testing notes

Publication details

Authors
Lubrizol
Publisher
Lubrizol
Year
2023
Document number
22-2559
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lubrizol (2023). CompuZol Immersion Cooling: Material Compatibility Guide. Lubrizol. 22-2559. https://media.lubrizol.com/-/media/Project/Lubrizol-Corporation/Lubrizol/Master-Site/10-1-Lubrizol/Thermal-Management/Documents/Compuzol-Immersion-Cooling-Compatibility-Guide.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.