Liquid Cooling for Data Centers: pH and Conductivity Measurement in Glycol-Based Coolant Loops
METTLER TOLEDO · Bryant Wai
A METTLER TOLEDO application page on interpreting pH and conductivity in glycol-based cooling loops; conductivity is affected by inhibitor and buffer additives and should be tracked as a trend against a defined baseline.
On this page
Overview
The manufacturer application page covers interpreting pH and conductivity measurement in glycol-based coolant loops of liquid-cooled data centers. Because conductivity is influenced by inhibitor and buffer additives in the fluid, it should be followed as a trend against a defined baseline rather than against an absolute threshold alone.
pH assessment should be made together with the operating range of the fluid formulation and other quality indicators. The general alarm examples on the page should not be taken as universal limits for every fluid; limits depend on the fluid maker's formulation.
Key points
- The subject is interpreting pH and conductivity in glycol-based coolant loops.
- Conductivity is affected by inhibitor and buffer additives.
- Conductivity should be monitored as a trend against a defined baseline.
- pH assessment should be made with the fluid formulation's operating range and other quality indicators.
Using it in design
- At commissioning record the fluid's baseline conductivity and pH and judge later measurements against that reference.
- Set alarm thresholds from the fluid supplier's formulation range, not from generic example values.
- Monitor pH and conductivity together with temperature, flow and other fluid quality indicators, not alone.
Who should read it
Engineers designing fluid quality monitoring and operations teams of liquid-cooled data centers.
Publication details
- Authors
- Bryant Wai
- Publisher
- METTLER TOLEDO
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Bryant Wai Liquid Cooling for Data Centers: pH and Conductivity Measurement in Glycol-Based Coolant Loops. METTLER TOLEDO. https://www.mt.com/us/en/home/library/applications/process-analytics/liquid-cooling-for-data-centers.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.