Technical guideFree to read2026

Storage joins the cooling loop: Designing SSDs for cold-plates

Micron · Ryan Meredith

A March 2026 Micron article showing that moving heat from 32 SSDs (800 W total) takes 38-81 W with air but 0.4-1.4 W with liquid, and that the single-sided 9650 E1.S SSD puts about 90% of heat-generating parts on the cold-plate side.

On this page

Overview

The article notes that an air-cooled 8-GPU system can fill 8U, while in emerging liquid-cooled servers the same configuration drops to 2U, so the 8 SSDs at the front are no longer in a spacious chassis but in a thermal environment where every watt of waste heat matters. It argues that storage has to take part in the cooling loop.

A technical brief models a server with 32 NVMe SSDs at 25 W each (800 W total) in two temperature scenarios: 11.1 °C and 8.3 °C between ambient and SSDs. Air cooling needs 38-81 W to move the heat; liquid cooling does the same job with 0.4-1.4 W, a reduction of about 98%. A cited Vertiv case study reports that raising liquid cooling from 0% to 75% cut total facility power by 10.7%.

A cold plate is a machined metal block with internal microchannels mounted to the SSD enclosure through thermal interface material (TIM); a coolant such as water-glycol takes the heat at the device and carries it to the facility loop. Spring-loaded cold plates with blind-mate quick-disconnect manifolds disconnect automatically when a drive is pulled, preserving hot-swap serviceability.

In conventional SSDs, heat-generating components sit on both sides of the PCB, so heat from the far side has to conduct through the board to a one-sided cold plate. The Micron 9650 NVMe Gen6 SSD (E1.S, 9.5 mm) concentrates about 90% of heat-generating components on one side, against roughly 60% in typical designs. The article is vendor content and the results rest on the manufacturer's technical brief.

Key points

  1. An air-cooled 8-GPU system fills 8U; in a liquid-cooled server the same configuration is 2U.
  2. Model: 32 NVMe SSDs at 25 W, 800 W total; ambient-to-SSD difference of 11.1 °C and 8.3 °C.
  3. Moving the heat takes 38-81 W with air and 0.4-1.4 W with liquid (about 98% reduction).
  4. Vertiv case study: liquid cooling from 0% to 75% cut total facility power by 10.7%.
  5. The Micron 9650 puts about 90% of heat-generating components on one side (typical design about 60%).
  6. Single-sided layout gives direct cold-plate contact, tighter NAND temperature uniformity and no throttling at Gen6 speeds.
  7. The standard E1.S (9.5 mm) form factor is hot-swap compatible with existing EDSFF liquid-cooled chassis.
  8. The Uptime Institute 2024 survey says about 20% of operators are deploying or planning liquid cooling.

Using it in design

  • In a liquid-cooled server specification, decide whether storage drives fall under the cold-plate scope and calculate the residual air load accordingly.
  • When selecting cold-plate-contact SSDs, prefer designs that concentrate components on one side and ask the vendor for throttling data.
  • Add blind-mate quick-disconnect sealing during drive swaps to acceptance testing.
  • Put the effect of fewer fans in the storage zone on power and noise into the hall energy model.
  • Treat SSD density being decoupled from airflow spacing as a design option as rack density targets rise.

Who should read it

Thermal engineers, server integrators and infrastructure designers working on liquid-cooled GPU servers and storage.

Document contents

  1. First, some cool math
  2. How cold-plate cooling works for SSDs
  3. The Micron 9650 NVMe Gen6 SSD: designed for liquid cooling
  4. What changes at the system level
  5. Looking ahead

Publication details

Authors
Ryan Meredith
Publisher
Micron
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Ryan Meredith (2026). Storage joins the cooling loop: Designing SSDs for cold-plates. Micron. https://in.micron.com/about/blog/applications/data-center/storage-joins-the-cooling-loop-designing-ssds-for-cold-plates

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.