High-Availability Data Centres: IT Cooling Connectors Whitepaper
Original title Addressing a strategic and economic challenge on a global scale: High-availability data centres
Stäubli
Stäubli's whitepaper on the role of quick-release couplings in data-centre liquid cooling, citing Tier availability levels (99.671% to 99.995%) and addressing hot swap, redundancy, sealing and energy efficiency.
On this page
Overview
The paper opens with the growth of the data-centre sector (4,500 facilities in 122 countries in 2020) and the cost of outages (EUR 11,000 per minute). It defines four needs: equipment reliability, higher storage density, equipment and data security, and energy efficiency. Under each heading it discusses what a liquid cooling coupling contributes.
Tier classes are summarised for availability: Tier 1 at 99.671% (about 28.8 hours of downtime a year), Tier 2 at 99.749%, Tier 3 at 99.982% (about 1.6 hours) and Tier 4 at 99.995% (about 25 minutes). It stresses that preventive maintenance, hot-swappable modules and redundant components only avoid downtime if connections can be separated and remade safely, even under pressure.
The technical argument rests on flat-face non-spill coupling design: no contamination enters the circuit and no fluid is lost on connection or disconnection, a smooth internal surface lowers pressure drop, and blind rack connections tolerate misalignment of up to several millimetres. It argues metal bodies outlast plastic and that total cost of ownership, not purchase price, should drive selection. The paper is vendor promotion; its figures are general industry statistics and it contains no product performance measurements.
Key points
- States 4,500 data centres in 122 countries in 2020, of which 1,800 in the USA.
- Tier 1: 99.671% availability (28.8 hours a year); Tier 3: 99.982% (1.6 hours); Tier 4: 99.995% (25 minutes).
- Quotes outage losses of EUR 11,000 per minute.
- Claims data-centre cooling systems use almost 50% of total electrical energy.
- Flat-face non-spill couplings avoid fluid loss and contamination on connect and disconnect, and lower pressure drop and pumping energy.
- Coupling misalignment compensation for blind rack mating reaches several millimetres.
- Hot swap and redundant modules require connections that can be separated safely on a pressurised line.
Using it in design
- Require non-spill, flat-face quick couplings at in-rack and manifold connections, and write fluid loss and air ingress during service into the specification.
- Include the coupling's pressure-drop contribution (Cv or flow-pressure curve) in pump calculations.
- For blind-mate rack modules choose couplings compatible with the guiding system, with misalignment compensation and seal material matched to the fluid.
- Confirm that redundant components can be serviced without isolating the line, in line with the target Tier.
Who should read it
Mechanical designers who select liquid cooling manifold and rack connections, and data-centre operations managers.
Document contents
- Data centres: exponential growth
- Equipment reliability
- Maximising data storage
- Guaranteeing equipment and data security
- Improving energy efficiency
Publication details
- Authors
- Stäubli
- Publisher
- Stäubli
- Year
- 2021
- Document number
- RX0930300A, 01/2021
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Stäubli (2021). Addressing a strategic and economic challenge on a global scale: High-availability data centres. Stäubli. RX0930300A, 01/2021. https://www.staubli.com/content/dam/fcs/brochures/whitepaper/it-cooling/Whitepaper-IT-cooling-connectors-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
