TotalEnergies DC COOLING BioLife: 100% Biosourced Single Phase Dielectric Fluid

Original title DC COOLING: 100% biosourced single phase dielectric fluid

TotalEnergies Fluids

TotalEnergies Fluids' technical brochure for its BioLife dielectric fluid: 100% biosourced from used cooking oil, 2-5 cSt viscosity at 40°C, flashpoint of at least 130°C and breakdown voltage above 35 kV.

On this page

Overview

The brochure presents the DC COOLING BioLife range that TotalEnergies Fluids developed for data-centre immersion cooling. The fluid is a single-phase dielectric liquid, 100% biosourced from used cooking oil, ISCC PLUS certified for full traceability. It rests on the immersion principle: submerging electronic components in a dielectric fluid to raise heat transfer.

Technical values are listed: very low viscosity of 2 to 5 cSt at 40°C, flashpoint of at least 130°C, breakdown voltage above 35 kV, electrical conductivity of 0 pS/m and specific heat of 2.32 kJ/(kg K) at 60°C. The maker also cites high metal compatibility, long-life stability and thermal and oxidation stability that it says will extend IT component life.

Under sustainability and HSE the fluid is described as non-toxic and non-irritant, readily biodegradable per OECD 301, with a favourable carbon footprint from a peer-reviewed cradle-to-gate life cycle assessment under ISO 14067. The document is a two-page product introduction; it does not give thermal conductivity, density or a material compatibility list.

Key points

  1. The fluid is 100% biosourced from used cooking oil, with ISCC PLUS traceability certification.
  2. Viscosity is 2-5 cSt at 40°C.
  3. Flashpoint is at least 130°C; breakdown voltage is above 35 kV; electrical conductivity is 0 pS/m.
  4. Specific heat is 2.32 kJ/(kg K) at 60°C.
  5. It is readily biodegradable per OECD 301, not toxic and not irritant.
  6. Carbon footprint is described as favourable from a peer-reviewed cradle-to-gate LCA under ISO 14067.

Using it in design

  • When selecting a single-phase immersion fluid, use the viscosity range (2-5 cSt) as an input to pump and tank convection design.
  • Record the flashpoint (≥130°C) and breakdown voltage as specification values in fire safety and electrical insulation review.
  • Ask the supplier for thermal conductivity, density and material compatibility data; the brochure does not give them.
  • Support biosourced and biodegradable fluid claims in corporate sustainability reporting with the certification documents.

Who should read it

Engineers selecting immersion cooling fluids and data-centre decision makers with sustainability targets.

Publication details

Authors
TotalEnergies Fluids
Publisher
TotalEnergies Fluids
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TotalEnergies Fluids DC COOLING: 100% biosourced single phase dielectric fluid. TotalEnergies Fluids. https://dxm.content-center.totalenergies.com/api/wedia/dam/variation/xysh7dg731tahsyyzwuo6gdrey/original%2Cdefault

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.