The data center industry has solved cooling. Now comes the hard part.
Vaisala · Anu Kätkä
A Vaisala expert article by Anu Kätkä argues that, as average rack density rises from 7 kW to 16 kW, measurement of temperature, pressure, flow, dew point and fluid health is the foundation of control in liquid-cooled facilities.
On this page
Overview
The article cites AFCOM's 2025 report: average rack density rose from 7 kW in 2021 to 16 kW, and 79 percent of respondents expect the climb to continue. At the leading edge, NVIDIA's 2027 Kyber rack platform is projected to reach 600 kW. The author states that air cooling reaches its practical limit at roughly 20 to 30 kW per rack; above that, fan energy alone makes air-only cooling unworkable and liquid becomes a physical requirement.
Running a liquid-cooled facility is described as a categorically different operating environment, needing new expertise in power, structural and mechanical engineering, fluid dynamics, chemistry and instrumentation. Air-side parameters such as temperature, relative humidity and differential pressure are standardized in ASHRAE guidance, while liquid cooling to the cold plates adds liquid temperature, pressure, flow, level, leak detection and coolant health indicators such as pH, turbidity, conductivity and refractive index.
Dew point is where risk concentrates: if pipe surface temperature falls below ambient dew point, water forms. The article gives standard practice as holding coolant supply temperature at least 2 °C above the measured ambient dew point, and notes that the CDU can keep that margin only if it continuously knows the dew point. Direct-to-chip cooling removes heat from the hottest components, but the remainder is still removed by air, so air-side management remains essential.
AI training workloads are intensive and intermittent: a cluster moves from idle to full load in minutes, and the cooling system must respond to the thermal step in real time. Without accurate real-time data, control runs on delayed or inaccurate information; inefficient cooling wastes energy, inadequate cooling risks hardware and overcorrection wastes both. The piece is a vendor expert article with no product table or accuracy data; it argues that measurement lets cooling be controlled precisely rather than conservatively.
Key points
- Per AFCOM 2025, average rack density rose from 7 kW in 2021 to 16 kW; 79 percent of respondents expect it to keep rising.
- NVIDIA's 2027 Kyber rack platform is projected to reach 600 kW.
- Air cooling's practical limit is roughly 20 to 30 kW per rack.
- Liquid cooling adds measurements: liquid temperature, pressure, flow, level, leak detection, pH, turbidity, conductivity and refractive index.
- Coolant supply temperature should be held at least 2 °C above the measured ambient dew point.
- With direct-to-chip cooling the residual heat is still removed by air, so air-side management remains necessary.
- AI workloads move from idle to full load in minutes; CDU control must be instant and continuous.
- Measurement quality is tied directly to operating results and is framed as a business decision.
Using it in design
- Define a control margin of at least 2 °C between coolant supply temperature and ambient dew point and provide continuous dew point measurement in the hall.
- Choose temperature, pressure and flow sensor locations and sampling rates for the CDU control loop around the fast step changes of AI load.
- Add level, leak detection and fluid-health indicators (pH, turbidity, conductivity) to the liquid-side measurement list.
- Calculate the residual air-side heat load of direct-to-chip racks separately and keep air-side measurement in place.
- Include sensor reliability and calibration in the maintenance programme as the basic input to cooling control.
Who should read it
Engineers designing CDU, monitoring and control systems for liquid-cooled data centers, and operations managers.
Document contents
- Rack density is rising
- From one domain to two
- Measurements in a liquid-cooled environment
- Dynamic facilities demand dynamic measurements
- What the next generation will require
Publication details
- Authors
- Anu Kätkä
- Publisher
- Vaisala
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Anu Kätkä The data center industry has solved cooling. Now comes the hard part.. Vaisala. https://www.vaisala.com/en/expert-article/data-center-industry-has-solved-cooling-now-comes-hard-part
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
