Technical guideFree to read2024

Vertiv CoolCenter Immersion Cooling System User Manual

Original title CoolCenter Immersion Soğutma Sistemi: Kullanım Kılavuzu (Orijinal Talimatlar)

Vertiv

Vertiv's 2024 manual (Turkish edition) describes the CoolCenter Immersion system with CDU and tanks for servers submerged in dielectric fluid; inlet water 12-35 °C, up to 4 tanks and detailed water quality limits.

On this page

Overview

The manual covers the CoolCenter Immersion system, which directly cools high-performance data centre servers: water or another liquid in the primary loop and dielectric coolant in the secondary loop. Servers are submerged in coolant in the tank for higher cooling efficiency than air convection, removing rack hot-spot concerns and spreading heat evenly across the server. Because the unit rejects heat with minimum difference from ambient, it can connect directly to dry coolers or cooling towers.

The system consists of a plate heat exchanger, circulation pump, filter, tank and connecting pipes; the primary (water) side of the heat exchanger connects to an external cooling source. In the modular unit system one CDU serves up to 4 tanks; the stand-alone unit has a single tank. Sensors include NTC temperature, liquid level and pressure sensors.

Operating requirements: indoor dry-bulb 5-40 °C, 20-80% RH, maximum wet-bulb 24 °C, inlet water 12-35 °C, altitude below 2000 m and 380-400 V (±15%) three-phase 50/60 Hz. Water quality limits include pH 6.5-8.5, conductivity <800 mS/cm, chloride <200 mg/L, sulfate <200 mg/L, total hardness <200 mg/L, ammonium <1 mg/L and free oxygen <1 mg/L; unsuitable water reduces performance and life. The manual covers installation, electrical, HMI, commissioning, server maintenance, filter and leak maintenance and fault diagnosis.

Key points

  1. The primary loop is water or another liquid; the secondary loop is dielectric coolant.
  2. In the modular system one CDU serves up to 4 tanks; the stand-alone unit has one tank.
  3. Inlet water temperature range is 12-35 °C.
  4. Operating environment: dry-bulb 5-40 °C, 20-80% RH, maximum wet-bulb 24 °C, altitude below 2000 m.
  5. Supply: three-phase 380-400 V (±15%), 50/60 Hz.
  6. Water quality: pH 6.5-8.5, conductivity <800 mS/cm, chloride <200 mg/L, sulfate <200 mg/L, total hardness <200 mg/L.
  7. Ammonium <1 mg/L and free oxygen <1 mg/L are required; performance and life suffer if water quality is not met.
  8. The unit can connect directly to dry coolers or cooling towers.
  9. Drain the system if it will be unused for a long time.

Using it in design

  • Select a dry cooler or cooling tower that keeps primary inlet water within 12-35 °C.
  • Specify primary water treatment against the pH, conductivity, chloride, sulfate, hardness, ammonium and oxygen limits.
  • Limit tanks per CDU to a maximum of 4.
  • Verify equipment room conditions (5-40 °C, 20-80% RH, wet-bulb 24 °C, altitude below 2000 m) on site.
  • Include the server maintenance hoist and service clearance requirements in the layout.
  • Plan leak and filter maintenance from the maintenance frequency table.

Who should read it

Engineers and field teams installing, commissioning and operating the immersion cooling system.

Document contents

  1. Important safety instructions
  2. Product overview
  3. Pre-installation preparation
  4. Mechanical installation
  5. Electrical installation
  6. HMI screen use
  7. Commissioning and maintenance
  8. Fault diagnosis and management
  9. Appendices: circuit diagrams, torque, operating menu, alarm output menu, accessory list

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2024
Document number
SL-71239_V1.1_10-24
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Vertiv (2024). CoolCenter Immersion Soğutma Sistemi: Kullanım Kılavuzu (Orijinal Talimatlar). Vertiv. SL-71239_V1.1_10-24. https://www.vertiv.com/48ecbc/globalassets/shared/sl-71239_v1.1_10-24_532_tk_web.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.