Vertiv SmartAisle Installation/User Manual
Original title Vertiv SmartAisle: Kurulum/Kullanım Kılavuzu
Vertiv
Vertiv's 2025 manual (Turkish edition) covers the SmartAisle edge data centre: 60-175 kVA IT load, N+1 redundancy, in-row cooling and APM2 UPS, with specifications, installation and operation.
On this page
Overview
The manual covers Vertiv SmartAisle, a pre-engineered, deployment-ready edge data centre with the critical components for power, cooling and continuous availability. It combines in-row air conditioners, in-row or external UPS and aisle containment, and houses EIA-310 compliant 19-inch IT equipment. Four models exist: SA1E08060MFB0 (60 kVA, 8 racks), SA1E08090MFB0 (90 kVA, 8 racks), SA1E11120MFB0 (120 kVA, 11 racks) and SA1E11175HFB0 (175 kVA, 11 racks).
In the specifications, average IT load per rack runs from 7.40 to 15.90 kVA, every model is N+1, with 380/400/415 V 3P/N/PE at 50/60 Hz. Power comes from Liebert APM2 UPS modules (30 or 60 kVA, 3 or 4 modules) with VRLA battery runtimes (EOL) of 15 or 11 minutes. Cooling uses R410A in-row Liebert CRD25 (25 kW) and CRD35 (36 kW) units with 20-100% capacity modulation and CCD25/CCD35 outdoor units (-35 to 48 °C); each enclosure has hot-aisle and cold-aisle emergency fans.
Environmental requirements include floor slope below 0.6 mm/m, at most 50 m equivalent horizontal distance between indoor and outdoor units, a -8 to 30 m height difference, indoor unit ambient 0-45 °C, 5-90% RH and altitude below 1000 m. Later chapters cover sliding door assembly, piping, power and data connections, network settings, the monitoring web interface, operation, maintenance and troubleshooting. It is a product installation and operation document, not a design guide.
Key points
- Four models: 60, 90, 120 and 175 kVA design IT load; 8 or 11 IT racks.
- Average IT load per rack ranges from 7.40 (60 kVA) to 15.90 kVA (175 kVA).
- All models are N+1; input 380/400/415 V 3P/N/PE, 50/60 Hz.
- UPS: Liebert APM2 30 or 60 kVA modules, 3 or 4 of them; VRLA battery end-of-life runtime 15 or 11 minutes.
- Cooling: R410A, CRD25 (25 kW) and CRD35 (36 kW) in-row units, capacity modulation 20-100%; test condition 37 °C return air and 35 °C outdoor.
- Outdoor units operate from -35 to 48 °C (with low-ambient kit).
- Installation limits: at most 50 m horizontal between indoor and outdoor units, height difference -8 to 30 m, floor slope below 0.6 mm/m.
- Aisle containment with in-row cooling is cited, from Uptime Institute data, as cutting energy use about 20% against average global PUE.
- Model weights are 4,858 to 9,473 kg (UPS and battery cabinets listed separately).
Using it in design
- When sizing an edge data centre, compare the model's average IT load per rack (7.40-15.90 kVA) with target density.
- Check floor loading for the 4,858-9,473 kg model weight plus UPS and battery cabinets.
- Verify the 50 m horizontal and -8/+30 m height limits when placing indoor and outdoor cooling units.
- Assess UPS battery time (11-15 min EOL) against load profile and generator start-up time.
- Audit the site for altitude below 1000 m, 0-45 °C indoor ambient and absence of corrosive gases.
Who should read it
Engineers installing and operating edge data centres, field installation teams and IT infrastructure managers.
Document contents
- Important safety instructions
- Introduction
- Installation
- Piping and cooling connections
- Cooling unit and UPS power connections
- Data communication connection
- Network settings configuration
- Navigating the monitoring unit web UI
- Operation
- Maintenance
- Troubleshooting
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2025
- Document number
- SL-71372 Rev A, 05/2025
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Vertiv (2025). Vertiv SmartAisle: Kurulum/Kullanım Kılavuzu. Vertiv. SL-71372 Rev A, 05/2025. https://www.vertiv.com/48ec49/globalassets/shared/sl-71372_reva_05-25_532_tk_web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.