Walther-Präzision Series CG-C: Blind-Mate Cooling Couplings
Original title Series CG-C: Low-pressure clean-break quick-connect coupling system
WALTHER-PRÄZISION
Walther-Präzision's CG-C series is a clean-break, low-pressure quick-connect coupling system with NW 6-16 nominal bores and working pressure up to 10 bar, presented for rack-mountable data-centre cooling modules and blind-mate uses.
On this page
Overview
The product page describes the CG-C series as a low-pressure clean-break (drybreak) quick-connect coupling system for direct installation in the customer's own systems, for water-based emulsions such as glycol-containing coolant. The valves close drip-free on disconnection and stay dry on both sides; during connection ingress of ambient air into the pipework is prevented.
Technical data: types CG-G06, CG-G09, CG-G12 and CG-G16; nominal bores NW 6, 9, 12 and 16; working pressure up to 10 bar depending on material; media cooling fluids and water; materials anodized aluminium, hard-coat anodized aluminium or stainless steel; seals optimised for the medium and operating temperature. Applications include automated connection of power modules to cooling circuits (railway), rack-mountable cooling elements in data centres and medical imaging.
The coupling is suited as a built-in, fail-safe component where the coupling state cannot be inspected directly (blind mating); on the nipple side a mounting sleeve gives automatic self-centring, while installation without it limits permissible angular and centre deviations. The page asks for manufacturer advice for coupling under residual pressure, pulsating pressure, non-lubricating media, highly viscous media, special cleanliness requirements and flow optimisation.
Key points
- Types CG-G06, CG-G09, CG-G12 and CG-G16; nominal bores NW 6, 9, 12 and 16.
- Working pressure is up to 10 bar depending on material.
- Materials: anodized aluminium, hard-coat anodized aluminium, stainless steel; seals chosen per medium and temperature.
- Clean-break valves close drip-free on disconnection and prevent air ingress into the pipework on connection.
- Fail-safe for blind-mate use; a mounting sleeve gives automatic centring.
- Manufacturer advice is requested for coupling under residual pressure, pulsating pressure, highly viscous media and special cleanliness needs.
Using it in design
- For blind-mate rack cooling modules select the nominal bore (NW 6-16) from flow and pressure-drop needs.
- Compare the 10 bar maximum working pressure with circuit pressure and pressure surges; consult the maker if pressure pulsates.
- Verify body material (aluminium or stainless steel) and seal material for compatibility with the coolant fluid.
- For blind mating reflect the mounting sleeve and permissible deviations in alignment and centring in the mechanical design.
Who should read it
Mechanical designers and product engineers selecting in-rack cooling module connectors.
Publication details
- Authors
- WALTHER-PRÄZISION
- Publisher
- WALTHER-PRÄZISION
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
WALTHER-PRÄZISION Series CG-C: Low-pressure clean-break quick-connect coupling system. WALTHER-PRÄZISION. https://www.walther-praezision.de/en/products/series-cg-c/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.