Technical guideFree to read

Uptime Institute 2026

Uptime Institute Tier Classification System

Model 'reliability.target' as an enum {TierI..TierIV} driving topology defaults: Tier I single path N; Tier II N+1 capacity components, single path; Tier III N+1 components AND two distribution paths (one may be passive), concurrently maintainable; Tier IV 2N or 2(N+1), two active physically compartmentalized paths and continuous cooling with UPS-backed pumps/fans.

  • Over 4,300 Tier Certification awards in 120+ countries (2026).
White paperPDF

Open Compute Project Foundation 2026

White Paper: Requirements for Energy Storage Systems Used in Data Centers, Revision 1.0, Version 1.0 (OCP Ready Facilities, January 2026)

Fix the ESS architecture (DC or AC coupled, distributed or centralised, backup-only or grid-interactive), write the applicable NFPA 70, NFPA 855 and IEC 62933 parts into the design basis, and consult the authority having jurisdiction (AHJ) early.

  • FM Global DS 5-33 (as cited) recommends battery installations in rooms with at least a 2-hour fire rating.