Technical guideFree to readYear not stated

Best Management Practice #10: Cooling Tower Management

U.S. Department of Energy / FEMP · U.S. Department of Energy Federal Energy Management Program (FEMP)

This US Department of Energy FEMP guide explains cooling-tower water losses, make-up water and concentration control, and ties blowdown management to water conservation.

On this page

Overview

The guide builds the tower water balance from three items: make-up replaces evaporation, blowdown and drift losses. Basin leaks or overflow add losses that must also be addressed. Measuring make-up alone therefore does not show how much of the water does useful work. A rise on the make-up meter therefore cannot be interpreted until it is split into evaporation, blowdown and leakage.

Cycles of concentration compare dissolved solids in blowdown and make-up water, and can be approximated by the make-up-to-blowdown volume ratio when other losses are negligible. If drift is neglected, make-up equals evaporation plus blowdown, so blowdown = evaporation / (cycles - 1); at 4 cycles, for example, blowdown is one third of evaporation. This derivation is a simple consequence of the relations, not the document's own statement.

The permissible concentration depends on source-water quality and treatment, so the guide does not impose one number. A tower balance is not whole-site WUE: water used in power generation and other uses sits outside it. Water savings are therefore sought in two steps: first the loss items (leaks, overflow) are closed, then the concentration cycle is raised up to the limit the treatment programme allows, which reduces blowdown.

Key points

  1. Tower make-up replaces evaporation, blowdown and drift losses.
  2. Basin leaks or overflow add losses that must also be addressed.
  3. Cycles of concentration compare dissolved solids in blowdown and make-up water.
  4. With other losses negligible, cycles can be approximated by the make-up-to-blowdown volume ratio.
  5. Permissible concentration depends on source-water quality and treatment.

Using it in design

  • Keep evaporation, drift, leaks and blowdown as separate items in the model.
  • Set the concentration limit with a water-treatment justification; do not hard-code a default.
  • Do not present the tower balance as whole-site WUE.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Mechanical designers and plant operators computing cooling-tower water balance and consumption.

Publication details

Authors
U.S. Department of Energy Federal Energy Management Program (FEMP)
Publisher
U.S. Department of Energy / FEMP
Year
Year not stated
Document number
FEMP BMP 10
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

U.S. Department of Energy Federal Energy Management Program (FEMP) Best Management Practice #10: Cooling Tower Management. U.S. Department of Energy / FEMP. FEMP BMP 10. https://www.energy.gov/cmei/femp/best-management-practice-10-cooling-tower-management

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.