Making AI Less 'Thirsty': Uncovering and Addressing the Secret Water Footprint of AI Models

Communications of the ACM (Association for Computing Machinery (ACM)) · Pengfei Li, Jianyi Yang et al.

Li, Yang, Islam and Ren set out a method for AI's operational water footprint: scope-1 on-site cooling water (WUE) plus scope-2 water embedded in electricity (PUE x EWIF). They apply it to GPT-3 training and inference and argue for reporting water alongside carbon.

On this page

Overview

The paper was published in Communications of the ACM in 2025 (vol. 68, no. 7, pp. 54-61); the arXiv:2304.03271 v5 preprint (26 March 2025) was read. Its DOI is 10.1145/3724499. The authors are Pengfei Li, Jianyi Yang, Mohammad A. Islam and Shaolei Ren. The method sums on-site cooling water (via WUE) and water embedded in electricity (via PUE x EWIF) and separates withdrawal from consumption.

The method is applied to GPT-3 training and inference across Microsoft US data-centre locations, and it projects global AI water withdrawal for 2027. Global AI demand is projected to account for 4.2-6.6 billion m3 of water withdrawal in 2027. Training GPT-3 in Microsoft's US data centres can consume 5.4 million litres of water in total, including 700,000 litres of scope-1 on-site consumption. GPT-3 'drinks' a 500 ml bottle for roughly 10-50 medium-length responses.

With good water quality, roughly 80% of cooling-tower withdrawal is evaporated (consumed). Data centres evaporate about 1-9 L per kWh of server energy, from 1 L/kWh (Google global annualised) to 9 L/kWh (a large Arizona facility in summer). Outside-air cooling with evaporative assist needs water when outside air exceeds about 85 F or is too dry, and about 70% of that added water is consumed, per Meta's report.

The US average electricity water intensity factor (EWIF) used is 3.14 L/kWh; in Table 1, total water per kWh ranges from 4.814 L (Iowa) to 9.629 L (Arizona). The spatial and temporal variation in WUE and EWIF makes 'when and where' a lever for water-aware scheduling and siting.

Key points

  1. Global AI demand is projected to account for 4.2-6.6 billion m3 of water withdrawal in 2027.
  2. Training GPT-3 in Microsoft's US data centres can consume 5.4 million litres of water in total, including 700,000 litres of scope-1 on-site consumption.
  3. GPT-3 'drinks' a 500 ml bottle for roughly 10-50 medium-length responses.
  4. With good water quality roughly 80% of cooling-tower withdrawal is evaporated; data centres evaporate about 1-9 L per kWh of server energy.
  5. Outside-air cooling with evaporative assist needs water above about 85 F or when air is too dry; about 70% of the added water is consumed (per Meta).
  6. US average EWIF is 3.14 L/kWh; in Table 1 total water per kWh ranges from 4.814 L (Iowa) to 9.629 L (Arizona).
  7. Water should be reported alongside carbon.

Using it in design

  • Separate withdrawal from consumption in water outputs, and default cooling-tower consumption to about 80% of withdrawal when water quality is good.
  • Use location-specific WUE and EWIF, and show how a site's monthly WUE varies through the year.
  • Support water-aware load placement and scheduling as an operations scenario for AI training halls.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Designers, sustainability analysts and researchers calculating the water footprint of AI data centers.

Related standards

  • ISO/IEC 30134-9 (WUE)

Publication details

Authors
Pengfei Li; Jianyi Yang; Mohammad A. Islam; Shaolei Ren
Publisher
Communications of the ACM (Association for Computing Machinery (ACM))
Year
2025
Document number
arXiv:2304.03271
Volume
68
Issue
7
Pages
54-61
Document language
English
Source type
Scientific
Access
Free to read
Licence
arXiv distribution permission — reuse conditions remain with the rights holder
Original licence note

Read via the arXiv v5 preprint (26 Mar 2025), which carries the arXiv default non-exclusive licence. Published version in Communications of the ACM (2025). Citation only.

Citation

Pengfei Li; Jianyi Yang; Mohammad A. Islam; Shaolei Ren (2025). Making AI Less 'Thirsty': Uncovering and Addressing the Secret Water Footprint of AI Models. Communications of the ACM (Association for Computing Machinery (ACM)). arXiv:2304.03271. 68(7), 54-61. https://doi.org/10.1145/3724499

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.