Castrol ON Immersion Cooling Fluid DC 15: Material Compatibility
Original title Castrol ON immersion cooling fluid: DC 15: Material Compatibility
Castrol
Castrol's material compatibility table for DC 15, a synthetic hydrocarbon immersion fluid: FKM, HNBR, PUR and ACM are good, NBR and PTFE moderate, and EPDM, silicone, PP and polyethylenes poor.
On this page
Overview
This one-page document rates the compatibility of Castrol ON DC 15, a synthetic hydrocarbon-based dielectric coolant, with elastomers and plastics on a three-level scale: good, moderate and poor. For moderate ratings the outcome depends on material grade and manufacturer, so the sheet asks that the exact grade be tested before use.
Among elastomers FKM, HNBR, polyurethane rubber (PUR), liquid fluoroelastomer (PFPE-Si) and acrylic rubber (ACM) are good; NBR and nitrile-bonded cork (TYM) are moderate; chloroprene (CR), EPDM and silicone rubber (VMQ) are poor. Among plastics ABS, boPET, polyester, POM, PA6 and PA66, PC, PS, hard PVC and PEEK are good; PTFE is moderate; PP, LDPE, HDPE and UHMW-PE are poor.
The document is a compatibility matrix; it does not carry fluid properties (viscosity, thermal performance), which sit in the product data sheet. A Castrol representative is the route for further information. The results are the manufacturer's own test data and do not replace system-level approval.
Key points
- Good elastomer compatibility: FKM, HNBR, PUR, PFPE-Si and ACM.
- NBR and nitrile-bonded cork (TYM) are moderate; results depend on grade and manufacturer.
- CR (chloroprene), EPDM and silicone rubber (VMQ) are poor.
- Among plastics ABS, boPET, polyester, POM, PA6/PA66, PC, PS, hard PVC and PEEK are good.
- PTFE is moderate; PP, LDPE, HDPE and UHMW-PE are poor.
- The sheet requires the exact material grade to be tested before use.
Using it in design
- If tank seals, hoses or cable insulation use EPDM or silicone, move to FKM, HNBR or PUR for use with DC 15.
- Exclude polyethylene and polypropylene pipe, tank internals or fittings as poorly compatible materials.
- Have moderate-rated materials (NBR, PTFE) tested by grade and manufacturer, and keep the test record in the design file.
- Prepare a list of all submerged parts and cross-check it against this table.
Who should read it
Mechanical designers and hardware integrators selecting materials for immersion tanks and IT equipment.
Publication details
- Authors
- Castrol
- Publisher
- Castrol
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Castrol Castrol ON immersion cooling fluid: DC 15: Material Compatibility. Castrol. https://www.castrol.com/content/dam/castrol/business-sites-new/en/global/corporate/documents/product/castrol-on/castrol-on-immersion-cooling-fluids-dc-15-compatibility.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.