Castrol ON Immersion Cooling Fluid DC 20: Material Compatibility
Original title Castrol ON immersion cooling fluid: DC 20: Material Compatibility
Castrol
Castrol's material compatibility table for DC 20, a synthetic hydrocarbon immersion fluid: aluminium, copper, nickel, steel, PTFE, PPS and polyamides are good; CR, NBR, POM and PVC moderate; EPDM and silicones poor.
On this page
Overview
The document rates the compatibility of Castrol ON DC 20, a synthetic hydrocarbon-based dielectric coolant, with metals, elastomers and plastics as good, moderate or poor. Moderate results depend on material grade and manufacturer, so testing of the exact grade before use is requested.
Among metals aluminium, copper, nickel, nickel-plated steel and steel are good. Among elastomers ACM, AEM, HNBR, PUR, FKM, fluorosilicone (FVMQ) and polyurethane are good; CR and NBR are moderate; liquid silicone rubber (LSR), silicone rubber (VMQ) and EPDM are poor. Among plastics PA46, PA66, PA6, PA12, polycarbonate, polyimide, PPA, PTFE and PPS are good; POM and PVC are moderate.
Compared with the DC 15 sheet, it covers metals and more elastomers such as CR, and rates PTFE as good. It is a compatibility matrix without fluid properties; the results are manufacturer test data and do not replace system approval.
Key points
- Good metal compatibility: aluminium, copper, nickel, nickel-plated steel and steel.
- Good elastomer compatibility: ACM, AEM, HNBR, PUR, FKM, FVMQ and polyurethane.
- CR and NBR are moderate; LSR, VMQ and EPDM are poor.
- Among plastics PA46, PA66, PA6, PA12, PC, PI, PPA, PTFE and PPS are good; POM and PVC are moderate.
- Moderate ratings depend on material grade and manufacturer.
- Unlike DC 15, PTFE is rated good with this fluid and CR is moderate.
Using it in design
- Use this table as the reference for direct contact of aluminium and copper heat exchangers, cold plates and pipe parts with DC 20.
- Replace seals, hoses and cable jackets containing silicone or EPDM with FKM, HNBR, ACM or FVMQ.
- Plan grade- and manufacturer-specific testing for POM, PVC, CR and NBR parts.
- Keep a submerged-parts list cross-checked against this table.
Who should read it
Mechanical designers and hardware integrators selecting materials for immersion systems.
Publication details
- Authors
- Castrol
- Publisher
- Castrol
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Castrol Castrol ON immersion cooling fluid: DC 20: Material Compatibility. Castrol. https://www.castrol.com/content/dam/castrol/business-sites-new/en/global/corporate/documents/product/castrol-on/castrol-on-immersion-cooling-fluids-dc-20-compatibility.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.