Regulation on the Fire Protection of Buildings (Binaların Yangından Korunması Hakkında Yönetmelik)
Original title Binaların Yangından Korunması Hakkında Yönetmelik
T.C. Cumhurbaşkanlığı / Bakanlar Kurulu
Turkey's main building fire code, setting for data centres the compartmentation of electrical and generator rooms, fire-stopping of cable penetrations and the design basis for gaseous suppression.
On this page
Overview
The Regulation on the Fire Protection of Buildings (Decision 2007/12937, Official Gazette 26735, 19.12.2007) is Turkey's main fire legislation and applies to the design, construction, operation and maintenance of all buildings. Data centre projects are directly subject to it.
On the electrical side, the regulation requires main electrical distribution rooms, in-building transformer and medium-voltage centres and generator rooms to have fire compartment walls and floors (Article 24(2)). Transformer room walls, floor and ceiling must have at least 120 minutes of fire resistance, and oil-filled transformers need an oil collection pit (Article 65). For generator rooms the walls, floor and ceiling must also have at least 120 minutes of resistance, with no water, waste, flammable liquid or gas piping passing through and no wet rooms above (Article 66).
Cable penetrations between fire compartments must be sealed with fire-stopping mortar, pillows, panels or similar elements (Article 69(1)). Gaseous suppression design is based on TS ISO 14520, with audible and visual pre-discharge warnings and automatic closing of vents and dampers on detection and discharge (Article 98(3)-(4)). Accredited oxygen-reduction systems may be used in normally unoccupied enclosed spaces such as IT system rooms (Article 98(6), added in 2015). Alarm and fault outputs of the gaseous suppression system must be connected to the fire alarm system with separate zone indication (Article 79(1)). Because the regulation addresses buildings in general, data-centre-specific detail should be read together with relevant standards and the fire authority's view.
Key points
- Main electrical distribution rooms, in-building transformer and MV centres and generator rooms must have fire compartment walls and floors (Article 24(2)).
- Transformer room walls, floor and ceiling need at least 120 minutes of fire resistance; oil-filled transformers need an oil collection pit (Article 65).
- Generator room walls, floor and ceiling need at least 120 minutes; no water, waste, flammable liquid or gas piping through it and no wet rooms above (Article 66).
- Cable penetrations between fire compartments must be sealed with fire-stopping mortar, pillows, panels or similar (Article 69(1)).
- Gaseous suppression design is based on TS ISO 14520, with audible and visual pre-discharge warnings and automatic closing of vents and dampers (Article 98(3)-(4)).
- Accredited oxygen-reduction systems may be used in normally unoccupied enclosed spaces such as IT system rooms (Article 98(6)).
- Gaseous suppression alarm and fault outputs must connect to the fire alarm system with separate zone indication (Article 79(1)).
Using it in design
- In the TR profile, default IT-room suppression to a TS ISO 14520 clean-agent design with damper-close interlocks.
- Offer oxygen-reduction (hypoxic) systems as an option for unoccupied rooms.
- Enforce 120-minute construction around transformer and generator rooms, with oil pits for oil-filled units.
- Flag any cable tray crossing a compartment line without a fire-stop element.
- Add connection of suppression alarm and fault outputs to the fire alarm system to the checklist.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Bring standards pre-checks into your project
Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.
Request a demo
Who should read it
Engineers designing data centre fire safety, electrical and generator rooms in Turkey, and project managers handling permits.
Related standards
- ISO 14520-1
- NFPA 2001
- IEC 60364-4-42
- ISO/IEC 22237-6
Publication details
- Authors
- T.C. Cumhurbaşkanlığı / Bakanlar Kurulu
- Publisher
- T.C. Cumhurbaşkanlığı / Bakanlar Kurulu
- Year
- 2007
- Document number
- Karar 2007/12937 (RG 26735, 19.12.2007)
- Document language
- Turkish
- Source type
- Turkish regulation
- Access
- Free to read
- Licence
- Bibliographic reference only — the document is not redistributed here; confirm reuse terms at the original source
Original licence note
Official Turkish legislation published in the Resmî Gazete; FSEK (Law 5846) Art. 31 makes laws and regulations freely reproducible, but this library keeps it citation-only by policy. Text read from mevzuat.gov.tr (consolidated version as of 2026-11).
Citation
T.C. Cumhurbaşkanlığı / Bakanlar Kurulu (2007). Binaların Yangından Korunması Hakkında Yönetmelik. T.C. Cumhurbaşkanlığı / Bakanlar Kurulu. Karar 2007/12937 (RG 26735, 19.12.2007). https://www.mevzuat.gov.tr/mevzuat?MevzuatNo=200712937&MevzuatTur=21&MevzuatTertip=5
Events on this subject
- Electricity Eurasia 2027
- ICCI 2027 – Uluslararası Enerji ve Çevre Fuarı ve Konferansı
- The smarter E Europe (Intersolar Europe, ees Europe, Power2Drive, EM-Power)
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.