Does the spread of direct liquid cooling make PUE less relevant?
Uptime Institute Journal (Uptime Institute) · J. Davis
An Uptime Institute Journal article arguing that direct liquid cooling (DLC) changes the energy profile so that PUE understates its benefits.
On this page
Overview
This article discusses how the spread of direct liquid cooling (DLC) affects the meaning of the PUE metric. Its core argument is that DLC changes a facility's energy profile, so PUE understates the benefit of the technology. It is a conceptual argument rather than a measurement study and was published in the Uptime Institute Journal. The argument centres on server fans. Server fan power is typically estimated at 5% to 10% of total IT power and is counted as part of IT load in PUE.
When DLC removes that fan power and reduces leakage power, IT energy falls. Because part of the facility load stays the same while the IT share shrinks, PUE can fail to improve or may even worsen, and partial PUE approaches its limit. The article states that most DLC implementations reach a partial PUE of 1.02 to 1.03, so the cooling side is already close to its floor. It notes that cold-plate systems still need some fans in power supplies and for low-power electronics.
It also recalls that PUE was developed by The Green Grid in 2007. It also cites survey data: for sites above 1 MW, only one in four respondents think air cooling will remain dominant beyond the next decade. As a limit, the piece is an opinion article; its message is that comparing DLC and air designs needs metrics beyond PUE.
Key points
- Most DLC implementations reach a partial PUE of 1.02 to 1.03.
- Server fan power is typically estimated at 5% to 10% of total IT power.
- DLC removes fan power (counted as IT) and reduces leakage power, so IT energy falls.
- Cold-plate systems still need some fans in power supplies and for low-power electronics.
- Only one in four respondents (>1 MW sites) think air cooling will remain dominant beyond the next decade.
- PUE was developed by The Green Grid in 2007.
Using it in design
- When comparing air and DLC options, report total facility energy and IT energy, not PUE alone.
- In DLC scenarios, subtract the server fan share (5-10%) from IT load before comparing.
- Note in reports that PUE loses discriminating power as partial PUE nears 1.02-1.03.
- In cold-plate designs, remember remaining fan loads such as power supplies.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers choosing between liquid and air cooling and engineers who report energy efficiency metrics.
Publication details
- Authors
- J. Davis
- Publisher
- Uptime Institute Journal (Uptime Institute)
- Year
- 2021
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Original licence note
Uptime Institute Journal article, copyright Uptime Institute, no open licence. Citation only.
Citation
J. Davis (2021). Does the spread of direct liquid cooling make PUE less relevant?. Uptime Institute Journal (Uptime Institute). https://journal.uptimeinstitute.com/does-the-spread-of-direct-liquid-cooling-make-pue-less-relevant/
Events on this subject
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
- Datacenter Forum Stockholm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.