National Laboratory of the Rockies (formerly NREL) 2026
High-Performance Computing Data Center Heat Capture and Reuse (ESIF)
In the heat-reuse module, support on-site end uses (low-temperature terminals, snow melt).
Collection
Direct-to-chip, immersion, CDUs and facility water interfaces.
49–72 / 153
National Laboratory of the Rockies (formerly NREL) 2026
In the heat-reuse module, support on-site end uses (low-temperature terminals, snow melt).
National Laboratory of the Rockies (formerly NREL) 2026
Use as a reference case for warm-water DLC presets (supply about 24 C, return about 38 C).
Open Compute Project Foundation 2025
In CDU catalogue entries, distinguish single-phase and two-phase (refrigerant type, saturation temperature, facility-water supply temperature).
Danfoss 2024
In the liquid-cooling catalogue store coupling size, OCP compliance, maximum working pressure, flow coefficient/pressure drop, disconnect-under-pressure limit and wetted materials.
Consulting-Specifying Engineer 2021
Offer integrated-free-cooling chillers as a catalogue option with the free-cooling changeover ambient field.
Consulting-Specifying Engineer 2025
Liquid-loop design rules: check pipe velocity <= 2.1 m/s above 3 in. NPS and TCS supply >= dewpoint + 2 C, and flag incompatible wetted materials.
Leibniz Supercomputing Centre 2025
Let liquid-cooled design templates allow facility supply temperatures up to 45 C with dry-cooler-only heat rejection, and show the resulting PUE.
Huawei Digital Power 2025
Import RD 01-21 as parametric AI-hall templates (rack kW, racks per module, module kW, redundancy of fan walls/TMUs/towers, generator and transformer counts) and as golden test cases for capacity math.
Cundall (for Iceotope Technologies) 2021
Catalogue liquid-cooled IT and CDUs with ASHRAE W-class and supply temperature fields, and use these to decide whether compressor cooling can be omitted for the site climate.
Applied Thermal Engineering (Elsevier BV) 2025
In hybrid immersion/direct liquid cooling design, rank dielectric fluids by FOM1, but remember a high-FOM1 fluid can infiltrate the TIM of cold-plated CPUs and raise their temperature.
Open Compute Project Foundation 2025
Give immersion tank and server catalogue items a field-reliability reference (AFR), and use component-level AFRs in the reliability module rather than assuming immersion degrades availability.
IEEE 2012
In liquid-cooling energy calculations, account for glycol concentration (higher pumping power, lower heat transfer) and flow-rate set points, not just supply temperature.
Energies (MDPI AG) 2019
Consider a cabinet-level rear-door heat exchanger as an option that can raise heat dissipation by 56-67% over air cooling; compare oil or water coolant separately on leakage risk and maintenance.
Uptime Institute Journal 2026
Catalogue DLC loops with coolant type (PG25/DI), filtration rating (default 25 micron) and wetted materials.
STULZ 2024
Model the per-rack heat split (liquid %/air %); it drives both CDU and CRAH sizing.
STULZ 2025
Define rack templates per GPU generation with a default kW and liquid/air split, for example 85/15 at 130 kW and 100/0 at 600 kW.
STULZ 2025
In the CDU selection tool let users trade approach temperature against heat-exchanger area and TCS delta-T, with Cases 1-3 as validation fixtures.
Energy Efficient HPC Working Group 2013
In commissioning checklists the tool generates for liquid-cooled plants, include verification that instrumentation matches manufacturer specifications.
ASHRAE 2013
In the DLC data model, keep facility water (FWS) and technology cooling system (TCS) loops separate, with a CDU as the interface.
WSP 2026
For TCS loops, add coolant fields (demineralised water, PG percentage).
Open Compute Project Foundation 2021
Add mechanical, hydraulic, electrical and network inspection protocols and a recorded pressure-decay test to the delivery and commissioning plan for rack acceptance.
Data Center Knowledge 2026
Add a retrofit check comparing liquid-cooled rack weight (default up to about 3,000 lb / 1,360 kg) with the raised-floor rating.
STULZ 2026
In the liquid-cooling module size TCS flow at about 1.5 L/min/kW by default and store CDU approach temperature and external static pressure.
Open Compute Project Foundation 2024
Store CDU capacity in the catalogue using this rating basis (kW at 5 C ATD, 1.5 LPM/kW, head and FWS impedance) so units from different vendors can be compared, and derate when the design ATD or flow differs.
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
Monthly newsletter · free
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.