Open Rack V3 Power Shelf Specification, Rev 1.0 (document dated 29 April 2025)
When choosing the feeding branch circuit, size option 1 for two independent 20 A NEC circuits or option 2 for a 32 A IEC circuit, check the 25 kA available short-circuit current at the outlet, and note there is no PDU in between.
- The 1 OU shelf measures 537 mm W x 46 mm H x 788.7 mm D.