Technical guideFree to read

Upsite Technologies blog 2014

4 Steps to Reducing Bypass Airflow

Compute CCF for each room from running cooling capacity and IT load and show it as a KPI, with a warning when it is high (oversupply).

  • CCF = rated capacity of running cooling units (kW) / (1.10 x IT critical load kW); the 10% covers lights, people etc.