313–336 / 418

Technical guidePDF

U.S. DOE FEMP / NREL 2024

Best Practices Guide for Energy-Efficient Data Center Design (Revised July 2024)

Weigh the supply air setpoint against server fan energy: raise it in small steps within the ASHRAE recommended range so the most demanding inlet nears 80 °F, only after air management is in place, and control to IT inlet temperature rather than return temperature.

  • Compute racks reached 60 kW in 2013, and recent liquid-cooled racks exceed 125 kW.
White paperFree to read

Schneider Electric 2013

Calculating Space and Power Density Requirements for Data Centers

Use this paper as the template for the Design Basis form: target average kW per rack, peak kW per rack (default 2x average), density uncertainty (default 15%), managed power ratio (default 0.7) and reserve space (default 15%).

  • Example overall target density: 5 kW per cabinet, about 160 W/ft2 (1,722 W/m2).
White paperFree to read

Schneider Electric 2011

Calculating Total Power Requirements for Data Centers

Use it as a quick-sizing calculator in novice mode: take IT kW, future kW, floor area, cooling type and UPS input type, and output service kW/A and generator kW, with the multipliers as editable defaults.

  • Actual IT power is roughly nameplate VA x 0.67.