Technical guidePDF

Open Compute Project Foundation 2022

Open Rack V3 Base Specification, Revision 1.0

In rack delivery and placement planning, check the 10-degree entry and 15-degree exit ramp angles, the 25.4 mm floor gap and the 4 mm step as rolling limits, and obtain door and shipping dimensions from the rack vendor separately.

  • The rack supports 48 mm OpenU or 44.45 mm EIA-310-D rack unit pitch.
White paperFree to read

Schneider Electric 2021

Rack Powering Options for High Density

In the rack power module, catalogue whip types, compute kW per whip as V x A x sqrt3 x 0.8 (three-phase) or V x A x 0.8 (single-phase), and default each rack to two three-phase whips (A/B).

  • Rack PDUs should be loaded to no more than 80% of rating.