arXiv (Texas Tech University) 2021
Short Circuit and Arc Flash Study on a Microgrid Facility
In a data-centre LV system with generator backup, run the arc-flash study for both grid-connected and islanded topologies, and check that the much lower islanded fault current (1,296 A instead of 22,793 A) does not lengthen clearing time.
- A factor of 1.4 was applied to the datasheet maximum short-circuit current of inverter-based sources as a safety band.