Electrical Efficiency Measurement for Data Centers
Never output a single PUE: produce a PUE-vs-IT-load curve (10-100%) and an annual PUE from hourly weather bins, labelling the averaging period explicitly.
- Using UPS output as IT load introduces a 2-25% error, which the model can subtract.