Research paperFree to readEditor’s pick

Journal of Science Policy & Governance (Journal of Science Policy and Governance, Inc.) 2026

Is Power Usage Effectiveness (PUE) Still Fit for Purpose? An Integrative Review of Data Center Metrics for Assessing the Environmental Impact of Modern AI Infrastructure

Give the sustainability panel at least four axes (PUE, CUE, WUE/WUEsource and a placeholder for IT productivity) and show them as a radar chart, so a low PUE never appears alone.

  • Water-energy tipping point: in a hot, dry climate a further 10% cut in water use can raise total energy use by 25%; in a cool, humid climate the cost is low.
Research paperFree to read

arXiv preprint (National University of Singapore) 2025

A Bidirectional Gated Recurrent Unit Model for PUE Prediction in Data Centers

For an operations or digital-twin module, use the feature list as a practical minimum sensor set for PUE prediction: outdoor dry/wet-bulb, IT power, UPS power, CRAC power/capacity/SCOP, coil temperatures and airflow.

  • RFECV selected feature sets of {21, 28, 29, 32, 33, 43} features with the minimum MSE.
Research paperPDF

Energies (MDPI AG) 2020

A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers

In high-density HAC halls, prefer a raised floor to hard-floor supply; on a hard floor high-velocity jets can starve the racks nearest the CRAHs and draw hot air back into them.

  • On the hard floor, supply velocities of 10 m/s or more persisted to the eighth rack position, versus the fourth with a raised floor.
Research paperPDF

arXiv preprint (Texas Tech University / PNNL; submitted to Renewable and Sustainable Energy Reviews) 2026

A Critical Review of Grid Integration Challenges and Flexibility Opportunities for Large-Scale Data Centers

Base interconnection studies on staged, updatable facility data rather than a single static MW value; requested peak MW and annual energy alone do not establish integration.

  • Under IEEE 519-2022, voltage-distortion limits at the PCC are the system owner's responsibility and current-distortion limits are the user's; a scalar THD cannot rule out narrow-band resonance.
Research paperPDF

Proceedings of the Twelfth ACM International Conference on Future Energy Systems (ACM) 2021

A Guide to Reducing Carbon Emissions through Data Center Geographical Load Shifting

For geographic load shifting, consider locational marginal carbon emissions (lambda-CO2) as the signal instead of LMP or regional average carbon intensity; it gave the largest reduction (-1.44%).

  • Lambda-CO2 shifting saved about 0.14 t CO2 per MW shifted and still reduced generation cost by 0.27%; LMP shifting cut cost by 1.07% but saved less carbon.
Research paperPDF

Energies (MDPI AG) 2023

A Review of Flywheel Energy Storage System Technologies

In UPS designs that only need bridging until the generator starts, evaluate a flywheel as a battery alternative, checking that a 15 s-15 min discharge range and a generator start under 10 s are adequate for the duty.

  • Flywheel operating temperature range is -40 to +50 °C, with low environmental requirements and no contamination.
Research paperPDF

Energies (MDPI AG) 2020

A Review of Lithium-Ion Battery Fire Suppression

In Li-ion UPS and BESS areas, set up detection with combined smoke-heat detectors; do not rely on heat detectors alone.

  • In DNV-GL tests, F500, FireIce, PyroCool foam, Stat-X aerosol and sprinklers all extinguished the fires, but the water-based systems cooled better over time.
Research paperPDF

Fluids (MDPI AG) 2026

A Review of Thermal Management in Modern Data Centres: Water Usage Effectiveness and Heat Transfer Coefficients

Set WUE targets from the heat-rejection topology (dry, free-cooling, hybrid, evaporative) and not only the server-side cooling technology; WUE depends on the share of heat rejected by evaporation.

  • Dry facilities with closed-loop liquid cooling need essentially no water, while evaporative systems typically report WUE up to 2.5 L/kWh.
Research paperPDF

Electronics (MDPI AG) 2025

A Systematic Review of Energy Efficiency Metrics for Optimizing Cloud Data Center Operations and Management

In efficiency reporting do not make PUE the only metric; knowing its weaknesses (manipulation, optimal-condition reporting, ignoring IT utilisation), complement it with WUE, CUE and IT-side metrics (SPUE, PpW, ITEE).

  • Google reported a 2023 fleet-average annual PUE of 1.10 against an industry average of 1.58; Microsoft reports PUE and WUE together.
Research paperPDF

Technology Review for Carbon Neutrality (Tsinghua University Press) 2025

Accelerating liquid cooling adoption in data centers: necessity, challenges and solutions

For racks where GPU/accelerator thermal design power exceeds 1,200 W, take liquid cooling as a mandatory design input, and weigh the initial cost (about 1.9-2.2 times air cooling) against TCO (up to 20% lower after 4 years, vendor figure).

  • Cooling systems in air-cooled data centres consume around 40% of total data-centre energy.
Research paperPDF

Applied Energy (Elsevier BV) 2025

Accounting carbon emissions from electricity generation: a review and comparison of emission factor-based methods

In data-centre carbon accounting, state the method (Tier 1, 2, 3) and factor source (IPCC or national) when choosing a grid emission factor; simple methods can underestimate generation emissions by about 73%.

  • AEF for the North zone by Method 5 rose from 0.1627 tCO2/MWh in 2016 to 0.4709 in 2022, then fell to 0.3936 in 2023.
Research paperFree to read

arXiv preprint (Cadence Design Systems) 2026

AI-driven Thermal-aware Data Center Capacity Planning

For layout iteration and add-load what-ifs, a surrogate that predicts only cabinet-inlet temperature (the compliance quantity) is cheaper and more accurate than full-field surrogates.

  • As a practical guideline, an initial dataset is about 500 simulation cases with around ten randomised parameters.
Research paperPDF

Energies (MDPI AG) 2018

Analysis of Air-Side Economizers in Terms of Cooling-Energy Performance in a Data Center Considering Exhaust Air Recirculation

In airside economiser design, plan exhaust grilles and the building envelope so recirculation stays below 5%; 15% recirculation raised energy about 6.1% for direct and 9% for indirect.

  • The authors recommend placing exhaust-air grilles so recirculation is below 5%, or handling it in the envelope plan at design stage.
Research paperPDF

ITEGAM- Journal of Engineering and Technology for Industrial Applications (ITEGAM-JETIA) (GN1 Sistemas e Publicacoes Ltd.) 2021

Analysis of Power Quality Parameters at Comparing UPS of Different Technologies

Choose online double-conversion UPS for loads where power quality improvement is expected; an offline UPS passes harmonics and unbalance through to the load side.

  • Output power factor: offline UPS 0.95, online UPS 0.97 (PRODIST range 0.92-1.00).
Research paperPDF

Standards (MDPI AG) 2026

Arc-Flash Hazards: Standards Development Framework in Facilities of National Importance in Healthcare and Data Centers

Schedule the arc-flash study after the coordination study and make that order a mandatory step in the project plan and model.

  • Example studies assumed available utility fault current of 21,000 A for the 440 V residential service and 21,000-40,000 A for the 480 V/1200 A commercial service.