Thermal Performance Evaluation of a Data Center Cooling System under Fault Conditions
Calculate the permissible time for a cooling outage with a pipe-volume energy balance and set the backup-cooling start time accordingly (here 300 s); high-temperature, contained designs give less time.
- From 18 °C chilled water and 25 °C supply air, coil capacity fell below the load and inlet temperatures rose rapidly.