ASHRAE 2008
High Density Data Centers - Case Studies and Best Practices (ASHRAE Datacom Series Book 7)
Use it as the source of reference layouts for high-density air-cooling templates.
- ASHRAE Datacom Series Book 7, product code 90441.
Collection
Technical references added to the library in the last 90 days.
361–384 / 1044
ASHRAE 2008
Use it as the source of reference layouts for high-density air-cooling templates.
U.S. DOE Federal Energy Management Program / Oak Ridge National Laboratory 2010
Place metering points in single-line and chilled-water diagrams according to the site, building, system and end-use levels.
Schneider Electric 2011
Offer a 'North America 415/240 V' one-line template (480 V UPS, auto-transformer RPP/PDUs, isolation transformer on UPS bypass) next to the traditional 480 to 208/120 V.
National Laboratory of the Rockies (formerly NREL) 2026
Model heat rejection as a priority chain (reuse, dry cooler, evaporative tower) with hourly switching.
National Laboratory of the Rockies (formerly NREL) 2026
In the heat-reuse module, support on-site end uses (low-temperature terminals, snow melt).
National Laboratory of the Rockies (formerly NREL) 2026
Use as a reference case for warm-water DLC presets (supply about 24 C, return about 38 C).
Open Compute Project Foundation 2025
In CDU catalogue entries, distinguish single-phase and two-phase (refrigerant type, saturation temperature, facility-water supply temperature).
Energies (MDPI AG) 2020
In selling data-centre waste heat, set heat-pump COP by cooling type (all-liquid 6.3, mixed 5.5, air-cooled 4.1) and include electricity price sensitivity in the feasibility study.
arXiv preprint (Texas A&M University) 2026
In power-chain loss calculators for AI halls, do not evaluate PSU, UPS and transformer efficiency only at average load; accept a load-profile descriptor (duty cycle, high/low power, frequency).
Vertiv 2024
Add a TEWI calculation to cooling options (refrigerant GWP, charge kg, leak rate, life years, grid emission factor).
Danfoss 2024
In the liquid-cooling catalogue store coupling size, OCP compliance, maximum working pressure, flow coefficient/pressure drop, disconnect-under-pressure limit and wetted materials.
Schneider Electric 2020
Add an on-site energy/DER layer: sources utility, diesel_standby, gas_chp, cchp_absorption, pv, wind, fuel_cell, bess with a continuous vs standby flag.
Schneider Electric 2023
Add tenantId and commercialStatus (open, closed, reserved, internal) to racks, cages and floor zones, with a floor-plan overlay coloured by status and per-zone remaining power, cooling and ports.
Schneider Electric 2026
Give every asset type, serial, rack/U location, network port, explicit A/B power path (rack PDU, UPS, PDU, switchgear) and cooling-unit dependency so the design exports as a DCIM digital twin.
Schneider Electric 2022
Add expected-life defaults to the asset catalogue (LV switchgear 15-25, MV switchgear 30-40, UPS 10-15 years), insulation medium for MV gear (SF6 or SF6-free), refrigerant with GWP for cooling units, and links to PEP/EPD documents.
Schneider Electric 2011
Give edge and closet room templates a default monitoring package: door switch, temperature at 3 heights, leak detector, camera, network management card on UPS and cooling, and metered/switched PDUs with sequencing.
Schneider Electric 2020
Add rack catalog fields: form, width, depth, height in U, static and dynamic load, UL 2416 and ISTA 3E flags, door perforation.
Consulting-Specifying Engineer 2021
Offer integrated-free-cooling chillers as a catalogue option with the free-cooling changeover ambient field.
Consulting-Specifying Engineer 2025
Liquid-loop design rules: check pipe velocity <= 2.1 m/s above 3 in. NPS and TCS supply >= dewpoint + 2 C, and flag incompatible wetted materials.
Schneider Electric 2014
Evaluate hot spots only at rack inlets against the selected ASHRAE class recommended range, not hot-aisle temperatures.
Vertiv 2023
Model UPS battery state of charge as partitioned: reserved backup energy used for autonomy checks plus an optional grid-service band.
Cummins 2007
Give the sizing engine inputs for minimum load %, maximum voltage and frequency dip, altitude and ambient derate, and per-load type (UPS rectifier pulses, VFD share, motor starting method).
Arup 2022
Include MEP items (generators, fuel tanks, UPS, switchgear, chillers, substations) in embodied-carbon estimates, not only structure.
Leibniz Supercomputing Centre 2025
Let liquid-cooled design templates allow facility supply temperatures up to 45 C with dry-cooler-only heat rejection, and show the resulting PUE.
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.