Schneider Electric 2013
Calculating Space and Power Density Requirements for Data Centers
Use this paper as the template for the Design Basis form: target average kW per rack, peak kW per rack (default 2x average), density uncertainty (default 15%), managed power ratio (default 0.7) and reserve space (default 15%).
- Example overall target density: 5 kW per cabinet, about 160 W/ft2 (1,722 W/m2).