Technical guidePDF

Open Compute Project Foundation 2026

OCP Cooling Environments: Cold Plate Sub-Project Design Specification, Universal Quick Disconnect (UQD), v2.0.0 (effective September 22, 2026)

Select size (02-08) by rack or server loop flow: rated flows run from 2.27 to 17.79 L/min; estimate pressure drop from the Cv range and ask for correction or extra testing where the fluid differs from water.

  • Cv ranges: 0.30-0.43 for size 02, 1.1-1.6 for 04, 2.2-3.3 for 06 and 3.6-5.6 for 08.
Technical guidePDF

Open Compute Project Foundation 2020

Design Guidelines for Immersion-Cooled IT Equipment, Revision 1.0 (December 2020)

Compare the bill of materials of a server to be immersed (cable jackets, heat-shrink, EPDM capacitors, CMOS battery, relays, thermal paste) against the paper's problem table and obtain a compatibility statement from the fluid supplier for each item.

  • In Soxhlet extraction testing, a mass loss below 2% indicates good material compatibility; the 48-hour test gives worst-case results.
Technical guidePDF

Open Compute Project Foundation 2022

Open Rack V3 Base Specification, Revision 1.0

In rack delivery and placement planning, check the 10-degree entry and 15-degree exit ramp angles, the 25.4 mm floor gap and the 4 mm step as rolling limits, and obtain door and shipping dimensions from the rack vendor separately.

  • The rack supports 48 mm OpenU or 44.45 mm EIA-310-D rack unit pitch.
Technical guidePDF

U.S. DOE FEMP 2010

Operations & Maintenance Best Practices: A Guide to Achieving Operational Efficiency, Release 3.0 (August 2010)

Choose maintenance strategy by equipment criticality: predictive for critical equipment with random failures, preventive for equipment subject to wear, reactive for small non-critical items; build a master equipment list and priority matrix.

  • Boiler combustion tuning and related O&M can yield fuel savings of 2% to 20%.
White paperFree to read

Schneider Electric 2021

Rack Powering Options for High Density

In the rack power module, catalogue whip types, compute kW per whip as V x A x sqrt3 x 0.8 (three-phase) or V x A x 0.8 (single-phase), and default each rack to two three-phase whips (A/B).

  • Rack PDUs should be loaded to no more than 80% of rating.