Research paperPDF

Energies (MDPI AG) 2019

Comparing Performance Metrics of Partial Aisle Containments in Hard Floor and Raised Floor Data Centers Using CFD

In airflow assessment do not rely on RCI alone; RCI of 100% coexisted with RTI of 40-50%, showing oversupply and bypass. Report RTI and per-rack Capture Index together.

  • With supply cut by 50%, RTI rose above 80%, and recirculation appeared in all containment variants while RCI still looked acceptable.
White paperFree to read

Schneider Electric 2011

Comparison of Static and Rotary UPS

Store UPS efficiency as a curve with at least 25/50/75/100% load points, plus storage type (battery, flywheel) and ride-through seconds.

  • Rotary can cost 40% more up front and is typically not modular.
Research paperPDF

Entropy (MDPI AG) 2019

Cooling Effectiveness of a Data Center Room under Overhead Airflow via Entropy Generation Assessment in Transient Scenarios

Use in the design rationale that aisle containment cut air-side entropy generation to negligible levels (0.15% and 0.03%), against 34% for an uncontained legacy room.

  • With containment, air-side entropy generation was only 0.15% (downward flow) and 0.03% (upward flow) of the total, against an earlier estimate of 34% for an uncontained legacy room.
Research paperPDF

Energies (MDPI AG) 2023

Cooling Technologies for Internet Data Center in China: Principle, Energy Efficiency, and Applications

In China, define project design targets from GB 50174-2017 temperature and humidity limits (18-27 °C, dew point 5.5-15 °C, RH at most 60%) and provincial PUE caps (for example Guangdong 1.25).

  • Cooling accounts for about 35-40% of total IDC energy consumption, the second largest consumer after IT equipment.
Research paperPDF

IEEE Transactions on Cloud Computing (Institute of Electrical and Electronics Engineers (IEEE)) 2026

Coordinated Cooling and Compute Management for AI Datacenters

Design AI-hall cooling control together with workload management: when GPU count and tensor parallelism, DVFS and supply air temperature and airflow were optimised jointly, cooling energy fell by 31.2%.

  • Cooling is cited as contributing approximately 45-50% of total energy consumption in AI data centres.
Research paperPDF

IEEE Transactions on Components, Packaging and Manufacturing Technology (Institute of Electrical and Electronics Engineers (IEEE)) 2021

CPU Overclocking: A Performance Assessment of Air, Cold Plates, and Two-Phase Immersion Cooling

For high-heat-flux chips, compare the point at which air cooling throttles (here 3.3-4 GHz) with the clock-rate gain from cold plates or 2P immersion (41-51%) in cooling technology selection.

  • Compared with air cooling, cold plates gave up to 41% and 2P immersion up to 51% higher CPU clock rates.
Technical guideFree to read

Lawrence Berkeley National Laboratory / U.S. Department of Energy 2017

Data Center Air Management Estimator, Version 1.0 (2017)

Offer a 'quick' airflow-management estimate mode with few inputs, consistent with the DOE AM Tool engine already in the library (engineering reference v3).

  • Distributed as an Excel file (AM Estimator Version 1-0), posted 06/27/2017.
Technical guideFree to read

Upsite Technologies blog 2019

Data Center Airflow Management at 100F

When high-temperature (A2/A3 allowable) set points are selected, report hot-hour and mechanical-cooling percentages from site weather.

  • Air-side economization hours above 90 F: Denver 111 (A2) / 226 (A3); Phoenix 694 / 1,817.
Technical guideFree to read

Eaton 2025

Data Center as a Good Grid Citizen

Add grid-code parameters to the utility connection object: UFLS stages, LVRT curve, post-fault power recovery ramp (%/s) and short-circuit ratio at the PCC.

  • Typical BESS Li-ion cells are limited to about 1C discharge.
StandardFree to read

ASHRAE / IBPSA-USA 2022

Data Center Chiller Plant: Simulation-based Comparative Control Design Case Study (2022 ASHRAE/IBPSA-USA Building Performance Analysis Conference and SimBuild)

Give cooling plant templates a control-sequence attribute (for example Guideline 36 condenser-water reset, economizer modes); it materially changes annual energy.

  • Alternative (Guideline 36-based) controls cut cooling energy 25% annually and about 18% in a typical summer.