Collection

Recently added

Technical references added to the library in the last 90 days.

Sources
1044
Downloadable PDFs
270
Years
1984–2027

All sources

697–720 / 1044

Research paperPDF

Frontiers in Toxicology (Frontiers Media SA) 2026

Toxicological and environmental evaluation of the two-phase immersion cooling fluid HFO-153-10mczz-E

When selecting a two-phase immersion fluid, add toxicology and occupational exposure limit (here WEEL 200 ppm) to the specification alongside boiling point (40-60 °C), dielectric strength, non-flammability and material compatibility.

  • HFO-153-10mczz-E meets the OECD structural definition of a PFAS and falls in the short-chain PFAS category.
Technical guideCitation

Trane Technologies / UL Environment 2023

Trane Centrifugal Chillers EPD 4790566295.101.1

In preliminary embodied-carbon calculations, use 129 kg CO2e per refrigeration ton as a proxy factor for water-cooled centrifugal chillers and label it as a proxy.

  • The source value is on page 14, Table 18; the declared unit is on page 2.
Research paperPDF

arXiv preprint (Nanyang Technological University / NVIDIA AI Technology Center) 2025

Transforming Future Data Center Operations and Management via Physical AI

For fast what-if analysis consider a CFD-trained surrogate (inference about 0.01 s), but state that the surrogate is only as accurate as the CFD it was trained on and is not validated against measurements.

  • The CapEx of building a data centre with 100k B200 GPUs is 4.5 to 5 billion US dollars and annual electricity OpEx can reach 400 million.
Technical guideFree to read

Cummins 2025

Transient Performance of Generating Sets

Store per generator the ISO 8528-5 class achieved, BMEP at rated load and the maximum single load step (%) that meets the stated dip limits.

  • DOL motor start draws about 4.5-8.5x FLC; star-delta about 2x FLC.
Research paperPDF

Electronics (MDPI AG) 2025

Two-Stage Power Delivery Architecture Using Hybrid Converters for Data Centers and Telecommunication Systems

In rack power-chain efficiency calculations, treat the number of stages and each stage's efficiency as separate inputs, and show the benefit of fewer stages at load points (low and high current).

  • End to end, direct conversion from about 110 VAC to 1 VDC peaked at 84.1% efficiency at 50 A and fell to 73.5% at 160 A.
Technical guideFree to read

Open Compute Project Foundation 2025

Unraveling the Efficiency, Performance and Sustainability Trade-Offs: Case Study of Liquid Assisted Air Cooling vs Traditional Air Cooling (OCP EMEA Summit 2025)

Distinguish LAAC (no facility water, heat still rejected to room air) from DLC with facility water in the server catalog, and do not reduce air-side cooling load for LAAC racks.

  • CPU, NIC and DC-SCM were cooler; DIMMs ran 3-6 C hotter and SSD/PSU temperatures rose.

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.