In the single-line editor, validate topology against the selected availability class (single path, redundant components, multiple paths, fault-tolerant).
Edition 1 published 2021-10-05, 35 pages; replaces ISO/IEC TS 22237-3:2018.
In the reliability module, add a resilience-level calculator that compares alternative power/cooling topologies on maintainability, recoverability and vulnerability.
Related: ISO/IEC 22237-1, EN 50600-4-31, IEEE 3006.7.
Tag each room in the floor plan with a protection class and check that access-control zones nest correctly, so a higher-class room is not reachable except through lower-class rooms.
Constructional requirements are given by reference to ISO/IEC 22237-2.
At operations handover, generate a capacity-planning and operations dataset (asset register, capacity headroom by power/cooling/space, maintenance windows) from the design model.
In the metrics module, define a single KPI boundary object (site boundary, measurement points, reporting period) reused by the PUE, REF, ERF, CER, CUE and WUE calculators.
Specifies a common structure for all other parts of ISO/IEC 30134.
In a heat-reuse calculator, compute ERF as exported heat, metered at the boundary heat exchanger, divided by total facility energy, on a range of 0 to 1.
In the water module, derive WUE (L/kWh_IT) from the hourly cooling model (evaporation, blowdown, humidification) and tag it with its measurement category.
Compute PCE automatically from the design model: utility/transformer capacity as P_facility, peak cooling electrical input at design ambient, UPS/transformer/busway losses and auxiliary panel loads, all on the declared redundancy basis.
Motor horsepower converts at HP x 0.746; kVA ratings convert to kW at the declared power factor.
Consider a cabinet-level rear-door heat exchanger as an option that can raise heat dissipation by 56-67% over air cooling; compare oil or water coolant separately on leakage risk and maintenance.
For simulated heat-source power of 800-1600 W, average heat-dissipation efficiency of the RDHE was 44.1%.
When a user selects a cooling topology, show a three-way comparison of energy (PUE), water (WUE) and carbon (CUE using local grid intensity) for the chosen site.
Danish hyperscale project with Fjernvarme Fyn: heat pumps lift to 70-75 C, expected 165,000 MWh/yr of heat at full build-out.