Technical guideFree to read

National Academy of Engineering, The Bridge (LBNL authors) 2026

Integrating AI Data Centers with the Power Grid

Expose flexibility capability per design (curtailable MW, BESS duration, on-site generation) as outputs for interconnection applications.

  • Published in The Bridge (National Academy of Engineering), LBNL authors, 2026.
Technical guidePDF

Open Compute Project Foundation 2026

Introducing Power Compute Effectiveness (PCE), a Provisioned Capacity Allocation Metric for the New Data Center Era (October 2026)

Compute PCE automatically from the design model: utility/transformer capacity as P_facility, peak cooling electrical input at design ambient, UPS/transformer/busway losses and auxiliary panel loads, all on the declared redundancy basis.

  • Motor horsepower converts at HP x 0.746; kVA ratings convert to kW at the declared power factor.
Research paperPDF

Energies (MDPI AG) 2019

Investigation of Heat Management in High Thermal Density Communication Cabinet by a Rear Door Liquid Cooling System

Consider a cabinet-level rear-door heat exchanger as an option that can raise heat dissipation by 56-67% over air cooling; compare oil or water coolant separately on leakage risk and maintenance.

  • For simulated heat-source power of 800-1600 W, average heat-dissipation efficiency of the RDHE was 44.1%.
Technical guideFree to read

Cundall 2024

Is power or water best for cooling?

When a user selects a cooling topology, show a three-way comparison of energy (PUE), water (WUE) and carbon (CUE using local grid intensity) for the chosen site.

  • Danish hyperscale project with Fjernvarme Fyn: heat pumps lift to 70-75 C, expected 165,000 MWh/yr of heat at full build-out.
Technical guideFree to read

Uptime Institute Journal (Uptime Institute) 2019

Is PUE actually going UP?

In a PUE benchmark display, show the survey average next to the hyperscale range.

  • Average PUE rose from 1.58 in 2018 to 1.67 in 2019 (sample of 624).