Huawei Digital Power 2025

Huawei AI Data Center Reference Design

Import RD 01-21 as parametric AI-hall templates (rack kW, racks per module, module kW, redundancy of fan walls/TMUs/towers, generator and transformer counts) and as golden test cases for capacity math.

  • Power distribution supports 2N, DR and BR architectures.
White paperFree to read

Schneider Electric 2015

Humidification Strategies for Data Centers and Network Rooms

Accept humidity limits as dew point plus RH in the environmental envelope settings, default to current ASHRAE recommended values rather than the 2011 ones quoted here, and recommend dew-point control mode for multi-CRAC rooms.

  • Static buildup: 250 V at 80% RH vs 12,000 V at 20% RH on a raised-floor tile; 1,500 V vs 35,000 V on synthetic carpet.
Technical guideFree to read

International Energy Agency 2025

IEA Energy and AI Observatory (data tool)

Link to the observatory from the tool's energy-context panel and take current national and regional data center demand figures from it rather than hard-coding values.

  • The related PDF reports are CC BY 4.0 and downloaded separately.
White paperFree to read

Schneider Electric 2013

Implementing Hot and Cold Air Containment in Existing Data Centers

Build a retrofit wizard asking aisle arrangement (hot/cold yes/no), raised floor (yes/no, depth), drop-ceiling return (yes/no), rack-top-to-ceiling clearance (mm), columns in rows, overhead cabling and existing cooler type, mapped to one of the six containment types.

  • Containment raises cooling-unit deltaT and can add about 20% or more cooling capacity.
Technical guideFree to read

Inform Elektronik 2025

Inform UPS - Uninterruptible Power Supply Catalogue

Keep module size, frame maximum, maximum parallel frames, output PF, online and eco efficiency, IEC 62040-3 class, overload curve points, THDi, altitude limit and battery string voltage options as UPS catalog fields.

  • Operating temperature 0-40 C; 20-25 C recommended for battery life.