TMMOB Makina Mühendisleri Odası (MMO) 2025

Testing-adjusting-balancing of data centres

In the commissioning module, include a TAB task list per cooling unit and hydronic circuit (design versus measured airflow, water flow, differential pressure, set points).

  • The reported outcome is a 10-25% energy efficiency improvement.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

White paperFree to read

Eaton 2018

What You Need to Know About Arc Flash

Add arc-flash attributes per switchboard (available fault current, clearing time, maintenance-mode/ZSI availability, working distance) and compute incident energy per IEEE 1584 for line and load side.

  • NFPA 70E 130.5(G): the incident energy analysis must be updated at least every 5 years.
White paperPDF

Open Compute Project Foundation 2022

White Paper: OCP Ready Data Centers - Program Mission, Methodology, and Case Studies, Revision 1.0 (June 2022)

Offer an 'OCP Ready' compliance profile that checks the delivery path (dock, ramps, door heights), floor load classes (uniform, concentrated, rolling), 3-phase IEC/NEMA rack circuits, hot/cold-aisle containment and generator load-acceptance time relative to BBU autonomy.

  • Design PUE ranges from 1.07 (Hydro66, WUE 0.059 L/kWh) to 1.6 (maincubes AMS01).
White paperFree to read

Rittal 2017

Whitepaper Rittal Liquid Cooling Packages

Catalogue close-coupled coolers by type (inline row, closed-loop rack, rear door, DX rack), rated kW, width, footprint, maximum air delta-T and water/refrigerant inlet temperatures.

  • Hybrid doors come in 10 kW and 20 kW versions and open 130 degrees.
White paperFree to read

Rittal 2014

Whitepaper Rittal PDU international

Keep PDU catalogue fields for phases, input A, max kW, outlet types, ambient rating, metering accuracy, relay type and management protocol (SNMPv3).

  • C14 inlets carry up to 10 A; C20 up to 16 A for large consumers.