1,044 sources

Sources

697–720 / 1,044 sources

Research paperPDF

Frontiers in Toxicology (Frontiers Media SA) 2026

Toxicological and environmental evaluation of the two-phase immersion cooling fluid HFO-153-10mczz-E

When selecting a two-phase immersion fluid, add toxicology and occupational exposure limit (here WEEL 200 ppm) to the specification alongside boiling point (40-60 °C), dielectric strength, non-flammability and material compatibility.

  • HFO-153-10mczz-E meets the OECD structural definition of a PFAS and falls in the short-chain PFAS category.
Technical guideCitation

Trane Technologies / UL Environment 2023

Trane Centrifugal Chillers EPD 4790566295.101.1

In preliminary embodied-carbon calculations, use 129 kg CO2e per refrigeration ton as a proxy factor for water-cooled centrifugal chillers and label it as a proxy.

  • The source value is on page 14, Table 18; the declared unit is on page 2.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

Research paperPDF

arXiv preprint (Nanyang Technological University / NVIDIA AI Technology Center) 2025

Transforming Future Data Center Operations and Management via Physical AI

For fast what-if analysis consider a CFD-trained surrogate (inference about 0.01 s), but state that the surrogate is only as accurate as the CFD it was trained on and is not validated against measurements.

  • The CapEx of building a data centre with 100k B200 GPUs is 4.5 to 5 billion US dollars and annual electricity OpEx can reach 400 million.
Technical guideFree to read

Cummins 2025

Transient Performance of Generating Sets

Store per generator the ISO 8528-5 class achieved, BMEP at rated load and the maximum single load step (%) that meets the stated dip limits.

  • DOL motor start draws about 4.5-8.5x FLC; star-delta about 2x FLC.
Research paperPDF

Electronics (MDPI AG) 2025

Two-Stage Power Delivery Architecture Using Hybrid Converters for Data Centers and Telecommunication Systems

In rack power-chain efficiency calculations, treat the number of stages and each stage's efficiency as separate inputs, and show the benefit of fewer stages at load points (low and high current).

  • End to end, direct conversion from about 110 VAC to 1 VDC peaked at 84.1% efficiency at 50 A and fell to 73.5% at 160 A.

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.